I build wire-sizing calculators for electricians, and the most common question I get is "why does your app say 12 AWG fails when 12 AWG is rated for 20 A?". The answer is voltage drop. Here is the exact math, so you can check any calculator, including mine.
The formula
For a single-phase circuit (120 V or 240 V):
VD = 2 × K × I × L / CM
- K: resistance of the conductor material in ohm-circular-mils per foot. About 12.9 for copper and 21.2 for aluminum at typical operating temperature.
- I: load current in amps.
-
L: one-way length of the run in feet. The
2already accounts for the trip out and back. - CM: conductor area in circular mils, from NEC Chapter 9, Table 8.
For a three-phase circuit, replace 2 with √3 ≈ 1.732.
Worked example: 20 A, 100 ft, 120 V, copper
| Wire | Area (cmil) | Drop (V) | Drop (%) |
|---|---|---|---|
| 12 AWG | 6,530 | 7.9 | 6.6 % |
| 10 AWG | 10,380 | 5.0 | 4.1 % |
| 8 AWG | 16,510 | 3.1 | 2.6 % |
For 12 AWG: 2 × 12.9 × 20 × 100 / 6530 = 7.9 V, and 7.9 / 120 = 6.6 %.
You can cross-check with the resistance column of Chapter 9, Table 8 instead of K: 12 AWG uncoated copper is 1.98 Ω per 1,000 ft, so 2 × 20 × 1.98 × 100 / 1000 = 7.92 V. Same answer.
What the NEC actually says about 3 % and 5 %
The familiar "3 % for a branch circuit, 5 % total for feeder plus branch" comes from Informational Notes in 210.19 and 215.2. Informational notes are recommendations, not enforceable requirements. A few articles do set mandatory limits (fire pumps in 695.7, for example), and some jurisdictions or engineers' specs adopt the 3 %/5 % figures, so check what applies to your job.
In practice: 12 AWG passes the ampacity check, but at 6.6 % drop a motor or compressor at the end of that run sees about 112 V instead of 120 V. That is where the complaints start.
Three mistakes I see in calculators
- Doubling the length twice. If you enter the round-trip length and the formula multiplies by 2, you get double the real drop.
- Using DC resistance for large AC conductors with poor power factor. For bigger feeders, Chapter 9, Table 9 (AC resistance and reactance) gives a more accurate result.
- Forgetting the ground wire when upsizing. If you increase the ungrounded conductors for voltage drop, 250.122(B) requires the equipment grounding conductor to be increased proportionally. Also check that the breaker and device terminals accept the larger wire.
Try it
I put this into a free web calculator that shows every step of the working: voltage drop calculator. The same math, plus wire size, conduit and box fill, is in my app Electrician Calculator NEC IEC (also on iPhone). No ads, no account.
If you spot a number that doesn't match your code book, tell me in the comments. That feedback is how I found the bug I wrote about last week.