By Chen Yu, ELV (extra-low-voltage) systems designer since 1998
I do not pick a fire-alarm battery from the panel brochure. The brochure tells me which block sizes the cabinet will accept. The size I need comes from the device list, the panel's own current, the standby and alarm durations the authority having jurisdiction has adopted, and a factor for a battery that is no longer new.
Over 25+ years of ELV and fire-alarm design on Grade-A design-institute projects, I keep seeing the same errors: sounder alarm currents left out, the panel treated as if it drew nothing, a 17 Ah block specified because "that is what we always use," and no allowance for end-of-life capacity.
Standby current and alarm current
Every device, and the panel itself, has two currents that matter:
- Standby (quiescent) current is what the system draws after mains failure, while it is still in the normal monitoring state: quiet detectors, the panel CPU, display, loops and comms, and normally-energized loads such as electromagnetic door holders.
- Alarm current is what the system draws in alarm: sounders, beacons, bells, voice-alarm amplifiers, detector alarm LEDs and alarm relays. Some loads fall. A door holder that drops out on fire alarm draws its current in standby, not in alarm.
The battery has to carry the standby load for the full standby period and then the alarm load for the alarm period. Both terms go into the amp-hour sum: do not size on the larger total alone, and do not assume alarm current is larger on every line. Use the manufacturer's data for the exact model, at the system voltage (most of the panels I specify are 24 V), not figures from the last job.
Standby time and alarm time
Write the two durations on the sheet before you touch a current. They come from the code the project is under, as adopted by the authority having jurisdiction. The figures below are starting points I confirm on every job, not clause citations: editions change, and national rules sit on top of the product standards.
- NFPA 72 is the usual U.S. reference. Many protected-premises systems are calculated for 24 h of standby followed by 5 min in alarm. Emergency voice/alarm communication systems are often calculated for 15 min in alarm. Read the edition the project names.
- BS 5839-1 is the usual U.K. installation code. A common starting point is 24 h of standby and 30 min in alarm. Where mains failure is not automatically transmitted to an alarm receiving centre, 72 h of standby is often required.
- EN 54-4 is the European power-supply equipment standard, and the reference I use for how the PSU and batteries are assessed, including capacity and ageing. Durations usually come from the national installation code, often 24 h + 30 min.
On work in China I also see GB 50116, often applied as 8 h standby plus 30 min alarm, which is why I do not copy a U.S. or U.K. duration onto a job under another national code.
The amp-hour formula
Ah_required = (I_standby * T_standby + I_alarm * T_alarm) * F
I_standby and I_alarm are the system totals in amperes. T_standby is the standby time in hours. T_alarm is the alarm time in hours, not minutes: 30 min = 0.5 h, 15 min = 0.25 h, 5 min = 5/60 h (about 0.083 h).
F is the ageing or derating factor. I use 1.25 unless the specification or the PSU/battery standard I am working to states another figure. That covers a VRLA block that will not deliver nameplate capacity at end of life. I write the factor on the sheet.
If the batteries will sit in a cold riser or an unheated box, I also apply the manufacturer's temperature-capacity curve (capacity is normally quoted at around 20 C). Low temperature cuts available amp-hours; high temperature shortens life.
Worked example (illustrative values only)
The figures below are example values, not a schedule you can copy onto a real panel. On a live job every current must come from the approved device data sheet.
Take a small two-storey office on a single 24 V addressable panel, required here to run 24 h standby and 30 min alarm, with F = 1.25.
| Device (example) | Qty | Standby each (mA) | Alarm each (mA) | Standby total (mA) | Alarm total (mA) |
|---|---|---|---|---|---|
| Addressable smoke detector | 40 | 0.25 | 4 | 10 | 160 |
| Addressable heat detector | 8 | 0.25 | 4 | 2 | 32 |
| Manual call point | 6 | 0.25 | 2 | 1.5 | 12 |
| Addressable sounder-beacon | 12 | 0.5 | 35 | 6 | 420 |
| Loop isolator | 4 | 0.4 | 0.4 | 1.6 | 1.6 |
| Electromagnetic door holder | 8 | 50 | 0 | 400 | 0 |
| Fire alarm panel | 1 | 180 | 280 | 180 | 280 |
| Remote repeater | 1 | 40 | 50 | 40 | 50 |
| System total | 641.1 | 955.6 |
So I_standby = 0.641 A and I_alarm = 0.956 A.
Ah_required = (0.641 * 24 + 0.956 * 0.5) * 1.25
= (15.384 + 0.478) * 1.25
= 15.862 * 1.25
= 19.83 Ah
The eight door holders, which draw nothing in alarm, are more than 60% of the standby current. Leave them out and the battery is undersized even if every sounder is correct. With modern low-current sounder-beacons the 24 h standby term usually dominates; a voice-alarm amplifier or a large conventional sounder circuit can jump the alarm current to several amperes, and the 5 or 30 min term then stops being a rounding error. The same device list at 72 h + 30 min would need about 58 Ah: a different cabinet and battery arrangement, not a slightly larger block.
Choosing the next standard battery size
I take the next standard VRLA size that is at least the calculated Ah. 7, 12, 17, 26 and 38 Ah are the sizes I see most often. For 19.83 Ah the next size is 26 Ah. A 17 Ah block would be short.
Voltage matters as much as amp-hours. Two 12 V, 26 Ah blocks in series give 24 V at 26 Ah, not 52 Ah. Parallel strings increase Ah, and only if the panel and charger are rated for that arrangement. I do not mix ages or capacities in the same string. The blocks also have to fit the enclosure or an approved battery box, and the charger must be able to recharge them in the required time.
Common mistakes
Forgetting the sounders' alarm draw. The battery looks fine on a quiet system and collapses a few minutes into a drill. Notification appliances, loop-powered or on a separate NAC, belong in the alarm total at alarm current, with every circuit included.
Ignoring the panel's quiescent current. A loop total is not a system total. The panel, repeaters and comms cards all draw current in standby. Use the manufacturer's figures for the actual configuration.
Sizing to nameplate capacity with no end-of-life factor. A 26 Ah block is not 26 Ah in year four. Omit F and you have sized a new battery, not the one that must still meet the duration at replacement.
Ignoring temperature. A block rated at 20 C and installed in a cold shaft will not deliver the calculated duration. High ambient temperature shortens life even when the capacity still looks comfortable.
Two more: treating two 12 V blocks in series as if the amp-hours add, and using 24 h + 5 min on a job that is actually under a 24 h + 30 min or 72 h rule.
Checklist
- Build a device list from the drawings, including the panel, repeaters and normally-energized loads such as door holders.
- Enter standby and alarm current for each line from the manufacturer's data at system voltage.
- Confirm standby hours and alarm minutes with the authority having jurisdiction and write them on the sheet.
- Calculate Ah as (I_standby * T_standby + I_alarm * T_alarm) * F, with T_alarm in hours and F stated (1.25 unless the specification says otherwise).
- Apply a temperature correction from the battery manufacturer's curve if the location is not a conditioned space.
- Select the next standard block size at the correct voltage and series/parallel arrangement.
- Check that the blocks fit the enclosure and that the charger can recharge them in the required time.
- Recalculate whenever the device schedule, sounder type or door-holder count changes.
None of this is difficult arithmetic. The work is in the device list, and in not borrowing durations or currents from another code or job.
Chen Yu has worked in ELV and intelligent-building design since 1998, delivering or supervising 200+ projects for courts, public-security organs, hospitals, schools, metro lines and industrial parks, and producing more than 30,000 CAD drawings, BoQs and tender documents with Grade-A design institutes in China. Portfolio: https://leoa81761-ops.github.io/
I packaged this calculation into a spreadsheet: the Fire Alarm Battery & Device Load Calculator (Excel) ($9). There is also a free ELV Quick Calculator Lite, and the full set of my ELV Excel sheets is in the ELV Excel library bundle.