A cooling tower rejects heat by evaporating water into the air. At altitude, the air is thinner. Less mass flow = less evaporation = less cooling.
The capacity loss
Altitude Air Density Tower Capacity (vs sea level)
──────────────────────────────────────────────────────────
Sea level 1.225 kg/m³ 500 tons (100%)
2,000 ft 1.155 kg/m³ 475 tons (95%)
5,000 ft 1.005 kg/m³ 425–450 tons (85–90%)
7,500 ft 0.900 kg/m³ 390–410 tons (78–82%)
A 500-ton tower at sea level delivers 425–450 tons at 5,000 ft. That is 50–75 tons of missing heat rejection.
Why: the density equation
ρ = P / (R × T)
Sea level: P = 101,325 Pa → ρ = 1.225 kg/m³
5,000 ft: P = 84,556 Pa → ρ = 1.005 kg/m³
Ratio: 1.005 / 1.225 = 0.82 (18% less mass per ft³)
The tower fan moves the same CFM but each cubic foot carries 18% less air mass. Less mass = less evaporative cooling.
The chiller penalty
The chiller rejects heat to condenser water. The tower cools that water. If the tower cannot reach design temperature:
Design condenser water: 85°F leaving tower
Actual at altitude: 88°F leaving tower
Delta: +3°F
Every extra degree of condenser water:
+1°F → +1–2% compressor energy
+3°F → +3–6% compressor energy
Over a cooling season (3,000 hours):
500-ton chiller at 0.55 kW/ton = 275 kW
+5% penalty = 13.75 kW additional
13.75 kW × 3,000 hrs = 41,250 kWh
41,250 × $0.12 = $4,950/year extra energy
The double hit
At altitude, both sides of the HVAC plant lose capacity simultaneously:
Air side:
Fan delivers same CFM but 18% less mass flow
Sensible heat formula: Q = 1.08 × CFM × ΔT
The 1.08 drops to ~0.89 at 5,000 ft
Result: 18% less cooling from air handling units
Condenser side:
Cooling tower rejects 10–15% less heat
Condenser water returns 2–4°F warmer
Chiller efficiency drops 3–6%
Result: higher energy cost per ton of cooling
Both hit at once. The building cannot hold setpoint AND the energy bill is higher than projected.
When to correct
Below 2,000 ft: correction usually unnecessary
2,000–4,000 ft: check tower selection data for altitude
Above 4,000 ft: always correct towers, fans, and gas equipment
Above 6,000 ft: significant — 20%+ air-side, 10%+ tower
The correction method
1. Calculate actual air density at altitude and design temp
2. Apply density ratio to tower selection (derate published capacity)
3. Apply density ratio to air-side calculations (adjust 1.08 constant)
4. Check chiller selection at corrected condenser water temp
5. Verify total plant capacity covers building load at altitude
Top comments (0)