Quick Tip: Why Your Economizer Misses Free Cooling Hours — Dry-Bulb vs Enthalpy Control

An economizer uses outdoor air instead of the compressor when conditions are favorable. But the controller decides when "favorable" means — and the wrong control strategy leaves free cooling on the table.

Two control strategies

Dry-bulb control:
  IF outdoor temp < setpoint (55-65F) → open dampers
  Simple, cheap, works in dry climates
  FAILS in humid climates (ignores moisture)

Enthalpy control:
  IF outdoor enthalpy < return air enthalpy → open dampers
  Accurate, captures both temp + moisture
  Requires humidity sensor ($300 per location)
Enter fullscreen mode Exit fullscreen mode

The problem with dry-bulb

Return air: 75F, 45% RH → enthalpy = 27.5 BTU/lb

Outdoor conditions:
                              Enthalpy   Dry-Bulb    Free
  Condition                   (BTU/lb)   Says...     Cooling?
  ──────────────────────────────────────────────────────────
  45F, 50% RH                  13.2      YES (< 55)   YES ✓
  55F, 60% RH                  19.8      NO (= 55)    YES ✗ missed!
  58F, 70% RH                  23.1      NO (> 55)    YES ✗ missed!
  62F, 80% RH                  27.0      NO (> 55)    YES ✗ missed!
  65F, 85% RH                  28.7      NO (> 55)    NO ✓
  70F, 70% RH                  29.4      NO (> 55)    NO ✓
Enter fullscreen mode Exit fullscreen mode

Three conditions with free cooling available — dry-bulb controller misses all three.

The dangerous case

60F, 95% RH → enthalpy = 26.1 BTU/lb

Dry-bulb controller: "60F > 55F → no economizer" ← correct!
But barely — enthalpy is close to return air.

Now: 60F, 40% RH → enthalpy = 19.5 BTU/lb
Dry-bulb controller: "60F > 55F → no economizer" ← WRONG!
8 BTU/lb of free cooling wasted.
Enter fullscreen mode Exit fullscreen mode

Same temperature, different humidity, opposite decisions needed. Dry-bulb cannot distinguish them.

Hours captured per year

Climate          Dry-Bulb Hours   Enthalpy Hours   Missed
──────────────────────────────────────────────────────────
Phoenix (dry)         2,800           2,900          100
Charlotte (mixed)     1,400           2,200          800
Atlanta (humid)       1,100           1,900          800
Houston (very humid)    600           1,200          600
Enter fullscreen mode Exit fullscreen mode

The math

800 missed hours × 15 tons avg × 1.2 kW/ton × $0.12/kWh
= $1,728/year in compressor energy that was not needed

Enthalpy sensor cost: $300 × 2 = $600
Payback: 4 months
Enter fullscreen mode Exit fullscreen mode

The rule

In dry climates (Phoenix, Denver): dry-bulb control is fine — humidity rarely matters.

In humid or mixed climates (anywhere east of the Rockies): enthalpy control captures 600-800 more free cooling hours per year. The sensor pays for itself in one season.

The decision is: is outdoor air enthalpy below return air enthalpy? Temperature alone cannot answer that question.