Who gets told when a zone on a monitored fire indicator panel in Western Australia is isolated? According to DFES, nobody: a fault on the same panel is passed on to the site's nominated contacts, but an isolation does not. That gap sits in the signal table DFES publishes for its Direct Brigade Alarm network, and it is where tenancy changes and fit-outs most often go wrong.
On a DBA-connected building, Fire Alarm Monitoring Services (FAMS), which runs the network on behalf of DFES, watches the panel through its Alarm Signalling Equipment (ASE). A detection alarm goes to the DFES Communication Centre for a crew turnout. A common fault goes to FAMS, which notifies the site's nominated contacts. An "Isolate Zone or Device" signal is listed with no action by either the Communication Centre or FAMS.
So an isolation is a local decision with no outside safety net. Someone on site switched part of the detection off, and the only way it gets switched back on is if a person remembers.
Who owns which decision
DFES is plain about where the responsibility sits. Its guidance says fire alarm maintenance and system performance are the responsibility of the building owner or manager, who must make sure the system complies with relevant Australian Standards including AS 1851, and stays suitable for the building's layout, use and occupancy as they change. Occupants, DFES says, do not manage fire alarm systems, but they play a role by following building procedures and reporting issues.
That split matters when a tenancy changes. The tenant's fit-out builder creates the dust, the owner or manager carries the system, and the fire services contractor does the hands-on work. DFES says each premises must engage its own fire services provider for installation, testing and maintenance, and that contractors connecting to the DBA network must be registered with either the Fire Protection Association Australia (FPAA) or the National Fire Industry Association (NFIA).
Checklist: before anyone touches the panel
Run these before a fit-out, shutdown or tenancy handover starts.
Who is allowed to isolate, and who signs it back on? Name one person for each. DFES advice for building works is to use detector covers, supervise contractors and isolate alarm zones during dusty work such as grinding, cutting or sanding. It does not say the isolation will undo itself.
Which zones, for how long? Limit the isolation to the zones the works actually affect, and write down the expected restore time before the first cut.
Will it run past 24 hours? DFES asks for a Fire System Impairment Notice when repair or maintenance work will keep a fire system below its required performance for more than 24 hours. Under the Building Regulations 2012, DFES says that responsibility lies with the building owner, local council or private certifier, the private alarm monitoring company where one is engaged, the property manager and other relevant parties. If the scheduled completion date passes and the system is still offline, a new form must be submitted.
What covers the gap? DFES notes an impairment may require additional safety and mitigation measures. Agree what those are for the isolated area before the works start, not after.
Are the right people listed? Fault notifications go to nominated contacts. DFES lists "DBA Changes (including owner/ biller changes)" among the jobs FAMS handles, and says false fire alarm invoices go to the entity registered with DFES as managing the alarm account. If the building has changed hands or managers, the account details need updating through the FAMS Customer Service Centre.
Checklist: when the panel shows a fault
Who gets the call, and what do they do next? A fault notification is only useful if the nominated contact knows which fire services contractor to ring and has authority to approve the callout.
Is the fault being isolated to make it go quiet? Isolating a faulty device stops the noise but also stops the detection. Record why it was isolated and who is chasing the repair.
Is the fault part of a pattern? DFES lists fire alarm system faults or failures, often from components that are not cleaned, maintained or replaced at end of life, among the main causes of false fire alarms. On a DBA site, a false alarm attendance can cost the owner or manager $1337 once the building passes three false alarms in a financial year, according to DFES.
Checklist: at tenancy handover
Is the panel back to normal? Every isolation from the fit-out should be restored, with the restore recorded. Since 1 May 2021, DFES says new ASE devices comply with AS 1670.3 2018, with Test Mode extended to 240 minutes and Isolate Mode no longer available on the ASE, so the isolation decision now lives at the panel and in the site's own records.
Does the system still suit the space? DFES says repeated alarms can point to detectors that do not suit the room, such as smoke detectors in kitchens or bathrooms. A new tenancy layout is the moment to check that the detection still matches how the space will be used.
Who does the new tenant report problems to? DFES directs occupants with maintenance concerns to the building owner or manager first. Put that contact in the tenancy pack.
Where the electrical scope fits
Most of this checklist is decided by owners, managers and their fire services contractor. The electrical side of a fit-out still has to be planned around it: which circuits feed the panel area, when works can be phased on an occupied site, and what commissioning records come back at the end.
Crossfire Electrical lists phased occupied-site works, facilities team coordination, commissioning records and supporting electrical scope for fire safety upgrades and fit-outs among its services for commercial and industrial sites across WA. If a tenancy change or fit-out is coming up on a site with fire detection, talk to Crossfire Electrical about scoping the dry fire and electrical work around the panel before the first zone is isolated.