DEV Community

Cover image for Fan Power in Python: Your Furnace Blower Is About 17% Efficient
Evgenii Konkin
Evgenii Konkin

Posted on

Fan Power in Python: Your Furnace Blower Is About 17% Efficient

The fan power equation fits on one line, and almost everyone feeds it the wrong efficiency.

HP = CFM × ΔP (in.w.c.) / (6356 × efficiency)
Enter fullscreen mode Exit fullscreen mode

The constant 6356 turns cubic feet per minute times inches of water column into horsepower. The numerator is the useful work done on the air. Everything else is the efficiency term, and for a home furnace blower that term is much smaller than the 55–65% you see for a bare forward-curved wheel in a fan catalog.

Here is a quick way to see it, using one measured operating point from Lawrence Berkeley National Laboratory's furnace blower tests (Walker, LBNL-58742, 2005): a PSC blower moving about 1,095 CFM at 0.8 in.w.c. drew about 610 W at the wall.

HP_W = 745.7  # watts per horsepower

def fan_hp(cfm, in_wc, eff):
    return cfm * in_wc / (6356 * eff)

def fan_w(cfm, in_wc, eff):
    return fan_hp(cfm, in_wc, eff) * HP_W

def eff_from_watts(cfm, in_wc, watts):
    """Back out wire-to-air efficiency from a measured draw."""
    return fan_w(cfm, in_wc, 1.0) / watts

print(f"{fan_w(1095, 0.8, 1.0):.1f} W of air power")
print(f"{eff_from_watts(1095, 0.8, 610):.1%} wire-to-air")
print(f"{fan_w(1100, 0.5, 0.60):.0f} W if you assume 60%")
Enter fullscreen mode Exit fullscreen mode

Output:

102.8 W of air power
16.8% wire-to-air
108 W if you assume 60%
Enter fullscreen mode Exit fullscreen mode

The air only receives about 103 W. The other ~500 W are lost in the motor, the wheel and the cramped cabinet. LBNL reports peak overall (motor plus aerodynamic) efficiencies of roughly 25% for PSC blowers and 30% for production ECM/BPM blowers, dropping to 12–15% for PSC at 0.5 in.w.c. Plug a catalog-style 60% into the formula and the predicted draw comes out several times too low.

The winter twist: a dirty filter

A clogging filter raises the static pressure, and the two motor types react in opposite ways:

# constant-airflow ECM: holds 1,100 CFM, ESP 0.5 -> 0.8 in.w.c.
# 28% efficiency is illustrative (~3 CFM/W at 0.8 in, as LBNL measured)
for esp in (0.5, 0.8):
    print(esp, f"{fan_w(1100, esp, 0.28):.0f} W")
Enter fullscreen mode Exit fullscreen mode
0.5 230 W
0.8 369 W
Enter fullscreen mode Exit fullscreen mode
  • ECM (constant airflow): airflow stays put, so power scales with pressure: +60% here.
  • PSC: it can't hold airflow. It slides down its fan curve, moves less air and usually draws slightly less power. LBNL measured about 30% less airflow at 0.8 in.w.c. on two PSC furnaces. The cost shows up as a higher temperature rise across the heat exchanger, not on the electric bill.

So "my blower is using less power" is not always good news.

Illustrative example: 1,100 CFM and the +0.3 in.w.c. filter penalty are assumptions; the 610 W point and the efficiency ranges come from LBNL-58742.

Your turn: have you ever measured total external static pressure on your own furnace? What did the manometer read with a clean filter versus a month-old one?