Quick Tip: The 3 Multiplier That Undersizes Three-Phase Generators by 73%

Single-phase and three-phase kVA formulas differ by one multiplier: √3 (1.732). Use the wrong one and you undersize by 42% — or oversize by 73%.

The two formulas

Single-phase:
  kVA = V × I / 1,000
  kW  = V × I × PF / 1,000

Three-phase:
  kVA = V × I × 1.732 / 1,000
  kW  = V × I × 1.732 × PF / 1,000
Enter fullscreen mode Exit fullscreen mode

The ONLY difference is × 1.732 for three-phase.

The mistake

200A, 480V, three-phase panel:

Wrong (single-phase formula):
  kVA = 480 × 200 / 1,000 = 96 kVA
  kW  = 96 × 0.85 = 81.6 kW

Correct (three-phase formula):
  kVA = 480 × 200 × 1.732 / 1,000 = 166.3 kVA
  kW  = 166.3 × 0.85 = 141.4 kW

Error: 73% undersized
Enter fullscreen mode Exit fullscreen mode

A 100 kW generator ordered. Actual load: 141 kW. Overload shutdown on first test.

How to know which formula

2 poles on breaker → single-phase
3 poles on breaker → three-phase (× 1.732)

Nameplate says "1PH" → single-phase
Nameplate says "3PH" → three-phase

Voltage 208Y/120, 480Y/277, 600Y/347 → three-phase
Enter fullscreen mode Exit fullscreen mode

Quick reference: 480V three-phase at PF 0.85

Amps    kVA      kW
─────────────────────
100A     83 kVA    71 kW
200A    166 kVA   141 kW
400A    333 kVA   283 kW
600A    499 kVA   424 kW
Enter fullscreen mode Exit fullscreen mode

Quick reference: 208V three-phase at PF 0.85

Amps    kVA      kW
─────────────────────
100A     36 kVA    31 kW
200A     72 kVA    61 kW
400A    144 kVA   123 kW
Enter fullscreen mode Exit fullscreen mode

The rule

Before any kVA or kW calculation, check the phase. One multiplier changes the answer by 73%. For generators, that is the difference between a system that runs and one that trips on overload.