In a metal building, the cooling load peaks within an hour of peak sun. In a heavy concrete building, the peak shifts to late afternoon. The difference — thermal lag — changes equipment sizing.
Thermal lag by wall type
Construction Time Lag
──────────────────────────────────────────
Metal panel (lightweight) 0-1 hour
Wood frame + insulation 2-3 hours
4" concrete block 3-4 hours
8" concrete block 5-6 hours
12" poured concrete 7-8 hours
Brick veneer over block 6-8 hours
Heavy materials absorb solar heat, store it for hours, then release it to the interior.
Why the peak shifts
Lightweight metal building:
Sun heats wall → heat enters interior in <1 hour
Peak solar at noon → peak cooling load at 1 PM
Heavy concrete building:
Sun heats wall → concrete absorbs and stores heat
Heat enters interior 5-6 hours later
Peak solar at noon → peak cooling load at 5-6 PM
Real case: concrete office in Dallas
Hour Solar Wall Roof Internal TOTAL
────────────────────────────────────────────────────
Noon peak absorb enter 80% 38 tons
3 PM decline release start 100% 44 tons
5 PM low release peak 100% 47 tons ← ACTUAL PEAK
7 PM zero still still dropping 35 tons
Engineer sized at noon: 42 tons.
Actual peak at 5 PM: 47 tons.
Result: 11% undersized. West side 3°F above setpoint every afternoon.
Multiple components peak at different hours
Component Peak Hour (south/west exposure)
────────────────────────────────────────────────────────
East window solar 8-10 AM
South window solar 11 AM - 1 PM
West window solar 3-5 PM
Roof (metal deck) 12-2 PM
Roof (concrete) 4-6 PM
Wall (metal) 12-2 PM
Wall (concrete) 5-8 PM
People/lights/equip 9 AM - 5 PM
The total cooling load = sum of ALL components at EACH hour. The hour with the highest sum is the design hour — not the hour with the highest single component.
Lightweight vs heavyweight
Metal building:
+ Peak occurs near solar peak (predictable)
+ Load drops fast after sunset
- Load spikes quickly with sun angle changes
- Morning pre-cool needed less
Concrete building:
+ Morning stays cool longer (stored nighttime cool)
+ Load rises gradually
- Peak delays to late afternoon
- System must run later into evening
- Nighttime "coast-down" still releases stored heat
The rule
For lightweight construction, the noon load calculation is close to the peak. For heavyweight construction, run the calculation at every hour from noon to 8 PM. The peak is almost always in late afternoon — and it can be 10-20% higher than the noon value.