Dry-bulb temperature (what the thermometer reads) does not tell you how dangerous the heat is. Wet-bulb temperature does — because it captures both heat and humidity in one number.
Wet-bulb vs dry-bulb
Dry-bulb: air temperature measured by a standard thermometer.
Wet-bulb: temperature measured by a thermometer wrapped
in a wet cloth with air flowing over it.
If the air is dry → evaporation cools the cloth → WB < DB
If the air is saturated → no evaporation → WB = DB
The gap between dry-bulb and wet-bulb tells you how much evaporative cooling is possible.
Why wet-bulb matters for humans
Your body cools itself by sweating. Sweat evaporates and removes heat. The rate of evaporation depends on the wet-bulb temperature — not the dry-bulb.
Phoenix: 110F dry-bulb, 15% RH
Wet-bulb: 71F
Sweat evaporates rapidly → body cools effectively
→ Uncomfortable but survivable
Houston: 95F dry-bulb, 75% RH
Wet-bulb: 89F
Sweat barely evaporates → body cannot cool
→ Heat stroke risk, even at "lower" temperature
The hotter city (Phoenix) is safer because the air is dry enough for sweat to work.
NIOSH/OSHA heat stress thresholds
Wet-Bulb Risk Level Action
──────────────────────────────────────────────────
< 77F Safe Normal work
77-82F Caution Rest breaks needed
82-86F Danger Limit heavy work
86-90F Extreme danger Only light work, frequent rest
> 95F Fatal threshold Body cannot cool — death without shelter
At wet-bulb 95F, even a healthy person in the shade with unlimited water will die from heat because evaporation stops completely.
Why wet-bulb matters for cooling towers
Cooling towers reject heat through evaporation — the same mechanism as sweat. The tower can cool water down to within 5-7F of the wet-bulb temperature (this gap is called "approach").
City Dry-Bulb Wet-Bulb Tower Leaving Water
──────────────────────────────────────────────────────────
Phoenix 110F 71F 76-78F (excellent)
Denver 95F 62F 67-69F (excellent)
Atlanta 95F 78F 83-85F (adequate)
Houston 95F 82F 87-89F (marginal)
Miami 92F 80F 85-87F (marginal)
Singapore 90F 82F 87-89F (marginal)
Same tower. Same design. Completely different leaving water temperatures — driven entirely by wet-bulb.
Finding wet-bulb from dry-bulb and RH
Approximate formula (Stull, 2011):
WB ≈ DB × atan(0.151977 × (RH + 8.313659)^0.5)
+ atan(DB + RH) - atan(RH - 1.676331)
+ 0.00391838 × RH^1.5 × atan(0.023101 × RH)
- 4.686035
Or: read it from a psychrometric chart.
Or: use a calculator.
The rule
When evaluating heat danger (for workers) or cooling tower performance (for systems), use wet-bulb — not dry-bulb. A 95F day at 30% RH and a 95F day at 80% RH are completely different conditions. Dry-bulb treats them the same. Wet-bulb does not.