Pilz PNOZ s4 vs PNOZ X3: Safety Relay Wiring Schemes & E-Stop Architecture

Pilz PNOZ s4 vs PNOZ X3: Safety Relay Wiring Schemes & E-Stop Architecture

Functional machine guarding requires fail-safe evaluation of emergency stop pushbuttons, safety gates, and optical light curtains. Pilz PNOZ safety relays set the global benchmark for Category 4 / PLe (ISO 13849-1) and SIL 3 (IEC 62061) compliant emergency stop circuits.


1. Comparing PNOZcompact (s4) with Classic PNOZ (X3)

Specification Pilz PNOZ s4 (750104 / 751104) Pilz PNOZ X3 (774310 / 774318)
Housing Width Ultra-slim 22.5 mm Standard 45.0 mm
Safety Contacts 3 N/O instantaneous + 1 N/C auxiliary 3 N/O safety + 1 N/C auxiliary + 1 Semiconductor
Supply Voltage 24 VDC (Electronic power regulation) 24 VDC / 110-230 VAC multi-voltage options
Terminals Push-in spring or screw terminals Screw terminals
Operating Modes E-stop, safety gate, light curtain (OSSD) E-stop, safety gate (Monitored or automatic start)

Explore safety hardware and contactors on the AOCTRL Pilz Safety Catalog and AOCTRL Safety Automation Hub.


2. Dual-Channel E-Stop Wiring with Cross-Fault Detection

To achieve Category 4 architecture:

  1. Wire dual N/C contacts across terminals S11-S12 (Channel 1) and S21-S22 (Channel 2).
  2. The relay outputs pulsed test signals on S11 and S21. A short circuit between channels is instantly detected, dropping safety output contacts 13-14, 23-24, and 33-34.
  3. Wire feedback loop from downstream contactors into Y1-Y2 (PNOZ s4) or S33-S34 (PNOZ X3) for contact weld monitoring.

3. Procurement of Certified Safety Spares

Avoid production line shutdowns by sourcing factory-sealed Pilz, SICK, and Banner safety relays directly through AOCTRL Industrial Sourcing.