Delta T is the temperature difference between return air and supply air:
ΔT = T_return − T_supply
Normal ranges by system type:
System ΔT (°F)
──────────────────────────────────
Residential cooling (DX) 14–22
Gas furnace 40–70
Heat pump (heating) 25–35
Chilled water 10–12
Hot water boiler 20–40
Condenser water 10–15
What out-of-range delta T tells you
In cooling mode:
ΔT < 14°F → low refrigerant charge
excessive airflow
dirty evaporator coil
ΔT > 22°F → restricted airflow
dirty filter
frozen coil
In heating mode (gas furnace):
ΔT > 70°F → low airflow through heat exchanger
potential cracking risk
From delta T to capacity
Combine delta T with airflow to get sensible capacity:
Q (BTU/hr) = 1.08 × CFM × ΔT
Example:
CFM = 1,000
ΔT = 20°F
Q = 1.08 × 1,000 × 20
Q = 21,600 BTU/hr
Q = 1.8 tons
If the system is rated at 2 tons, it is delivering 90% of capacity. Normal.
If ΔT drops to 12°F:
Q = 1.08 × 1,000 × 12
Q = 12,960 BTU/hr
Q = 1.08 tons → 54% of rated capacity
Something is wrong. The homeowner feels it.
Two measurement rules
1. Supply temp: measure 6+ ft downstream from coil (not at coil exit)
2. Wait 15+ min after startup before reading (steady-state required)
Breaking either rule gives a false delta T.
Top comments (0)