DEV Community

Cover image for Quick Tip: Solar Gain Through Windows — The Cooling Load That Changes by the Hour
Evgenii Konkin
Evgenii Konkin

Posted on

Quick Tip: Solar Gain Through Windows — The Cooling Load That Changes by the Hour

Solar gain is the most variable component of cooling load. It changes with orientation, time of day, season, and glass type.

The formula

Q_solar = Window Area × SHGC × Incident Solar Radiation
Enter fullscreen mode Exit fullscreen mode

Where:

SHGC = Solar Heat Gain Coefficient (0 to 1)
       Modern low-e glass:   0.22–0.40
       Older single-pane:    0.65–0.85
Enter fullscreen mode Exit fullscreen mode

Orientation makes a 7x difference

Same 100 sq ft window, same building, same day (July, 4pm):

Orientation    Solar Gain (BTU/hr)    Why
──────────────────────────────────────────────────────
West           15,000–20,000          direct sun at hottest hour
South          8,000–12,000           sun high, partially blocked by overhang
East           3,000–5,000            direct sun was morning (already passed)
North          2,000–3,000            diffuse sky radiation only
Enter fullscreen mode Exit fullscreen mode

West is worst because peak solar and peak outdoor temperature hit at the same time.

The afternoon spike

8am–2pm:  building runs fine
3pm:      west offices start overheating
4pm:      supply air cannot keep up
5pm:      complaints, thermostat wars

Cause: solar gain was averaged in the calculation
       system sized for noon average, not 4pm peak
Enter fullscreen mode Exit fullscreen mode

SHGC comparison

For a 200 sq ft west-facing window at 4pm peak (100 BTU/hr/ft² incident):

Old single-pane (SHGC 0.75):
  Q = 200 × 0.75 × 100 = 15,000 BTU/hr

Modern low-e (SHGC 0.25):
  Q = 200 × 0.25 × 100 = 5,000 BTU/hr

Difference: 10,000 BTU/hr = 0.83 tons
Enter fullscreen mode Exit fullscreen mode

Replacing the glass cuts solar gain by 67% on that wall.

Shading effectiveness

External shading (overhang, fin):     blocks 50–90% of direct sun
                                      most effective on south walls
                                      ineffective on west (low sun angle)

Internal shading (blinds):            blocks 10–30% of heat gain
                                      solar energy already inside
                                      blind absorbs and re-radiates as heat
Enter fullscreen mode Exit fullscreen mode

External shading before the glass > internal shading after the glass. Always.

The quick check

If solar gain > 20% of total cooling load:
  → size system for 3pm–5pm peak, not noon average
  → check west-facing glazing separately
  → consider SHGC upgrade or external shading
Enter fullscreen mode Exit fullscreen mode